COMITRONIC SPEEDTRONIC N
COMITRONIC SPEEDTRONIC N Safety Modules / Safety Relays Johor Bahru (JB), Malaysia Supplier, Wholesaler, Supply, Supplies | CW Process Instrumentation Store
RM 2,300.00
1 in stock
  • Time before dangerous failure: MTTFd = 100 years
  • Cycle before dangerous failure: B10d=100,000 at 5A
  • Risk duration: approx. 2 to 7s adjustable at front
  • Persistence: approx. 20 mV to 700 mV adjustable front
  • Motor power: up to 3x690 VAC
  • Protection for severed wires: yes
  • Protection against disconnection of motor coiling: yes
  • Safety contacts: 3x NO 8A/250V redundant
  • Diagnostics: 1x NF 8A/250V redundant parallel.
  • 1 PNP ''OK'' output indicating motor coiling presence.
  • 1 PNP ''ERROR'' output indicating a synchronization malfunction.
  • 1 ''RS'' system reset input.
  • Indicators: 3 LEDs for diagnostics
  • Reset: automatic
  • Mounting: symmetrical DIN 35mm rail on DIN 50022
  • Mounting: IP 20 electrical box
  • Electrical connection: Maximum 14 AWG (2.08 mm²) / 250V minimum
  • Temperature: -20°C to +60°C

Please leave your enquiry here, we will reply as soon as possible.


*only support gif, jpeg, jpg, png, pdf
Switch To Desktop Version